Electronics and wiring
5.8 Running logic
Automatic Cooling Mode Operation Sequence
When running in Automatic Mode, unit stops operations every time cold-room reaches SP set-point temperature, waiting that
difference between TA actual and SP set-point temperatures exceeds dF differential to restart with required operations.
1
ON Signal.
1(’)-2 Starting Procedure.
2-3
Cooling Operations.
3
TA Cold-room temperature has
reached SP set-point value.
3-1’ Unit Stand-by, waiting for
cooling/heating request.
1’ TA Cold-room temperature is out
from admitted range (SP±dF).
4 OFF Signal.
Continuous Cooling Mode Operation Sequence
1 ON Signal.
1-2 Starting Procedure.
2-3 High Speed Pull Down.
3 TA-SP<ddF Engine decreases speed.
3-4 Unit Cools cold-room at Slow speed.
4 Unit starts to heat.
4-5 Unit Heats at Slow speed.
5 Unit starts to Cool.
5-4
Unit Cools at Slow speed.
2’
TA-SP>ddF Engine increases speed.
2’-3 High Speed Cooling.
6 Heating unit increases speed.
6-7
High Speed Heating.
7
Unit decreases speed.
7-5
Unit Heats at Slow speed.
8
OFF Signal.
Summary of Contents for un0 010
Page 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Page 4: ......
Page 15: ......
Page 16: ......
Page 17: ...Section1 Generalinformation...
Page 19: ......
Page 30: ......
Page 31: ...Section2 Descriptionoftheunit...
Page 33: ......
Page 45: ...34 Description of the unit 2 2 Evaporating section...
Page 46: ......
Page 47: ...Section3 CoolingCircuit...
Page 94: ......
Page 95: ...Section4 DieselEngine...
Page 97: ......
Page 130: ......
Page 131: ...Section5 ElectronicsandWirings...
Page 135: ......
Page 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Page 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Page 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Page 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Page 178: ......
Page 179: ...Section6 Alarms Troubleshooting...
Page 181: ......
Page 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Page 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Page 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Page 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Page 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Page 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Page 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Page 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Page 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Page 197: ......
Page 198: ......
Page 199: ...Annex1 Parameters...
Page 201: ......
Page 208: ......
Page 209: ......