SM-18001-rev.1
5-37
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(132) Not Prepared (r4)
(133) Not Prepared (r5)
(134) Not Prepared (r6)
(135) Not Prepared (r7)
(136) Not Prepared (r8)
(137) Not Prepared (r9)
(138) Not Prepared (rA)
(139) Not Prepared (rb)
(140) Not Prepared (S1)
(141) Not Prepared (S2)
(142) Not Prepared (S3)
(143) Not Prepared (S4)
(144) Not Prepared (S5)
(145) Not Prepared (S6)
(146) Not Prepared (S7)
(147) Not Prepared (S8)
(131) Setback Temperature Compensation (During card key removal, setpoint is setbacked) (r3)
This function is utilized to change the indoor temperature condition to Thermo-ON/OFF.
In case the setback operation is enabled and the card key is removed, setpoint is compensated and
fan operate at “LOW” speed.
By default,
Cooling: Se4
o
F (+2.5
o
C)
Heating: Setpoint -4
o
F (-2.5
o
C)
When the external signal is detected (card key is inserted), return to the original setting temperature.
Setting Condition
Actual Control Temperature
00 (Standard)
Wired Controller Setting Temperature (Indicated Value) +4
o
F (2.5
o
C)
01
Wired Controller Setting Temperature (Indicated Value) +5
o
F (3.0
o
C)
02
Wired Controller Setting Temperature (Indicated Value) +6
o
F (3.5
o
C)
03
Wired Controller Setting Temperature (Indicated Value) +7
o
F (4.0
o
C)
04
Wired Controller Setting Temperature (Indicated Value) +8
o
F (4.5
o
C)
05
Wired Controller Setting Temperature (Indicated Value) +9
o
F (5.0
o
C)
06
Wired Controller Setting Temperature (Indicated Value) +10
o
F (5.5
o
C)
07
Wired Controller Setting Temperature (Indicated Value) +1
o
F (0.5
o
C)
08
Wired Controller Setting Temperature (Indicated Value) +2
o
F (1.0
o
C)
09
Wired Controller Setting Temperature (Indicated Value) +3
o
F (1.5
o
C)
10
Wired Controller Setting Temperature (Indicated Value) +3
o
F (2.0
o
C)
Compensation for setback operation can be changed as shown in the table below.
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...