3-20
SM-18001-rev.1
TROUBLESHOOTING
1: Refer to Section 3.1.4 (3) above for details.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
Float Switch
Failure of
Float Switch
Failure of
Condensate
Pump
Contact Failure
Incorrect Connection
Failure
Contact Failure
Incorrect Connection
Failure
Check condensate pan.
Check drainage by
pouring water.
Check continuity
when condensate
level is low.
Measure resistance
with a tester.
Measure resistance
with a tester.
Measure voltage
between CN36 terminals
with a tester.
Check connection.
Check connection.
High
Condensate
Level
Clogging of
Drainage
Up-Slope
Condensate
Piping
Remove foreign
particles clogging
condensate pipe.
Replace float switch
if faulty.
Replace condensate
pump if faulty.
Replace and tighten
connector.
Replace and tighten
connector.
Repair connection.
Repair connection.
Check PCB in
Self-Checking Mode.
1
Replace it if faulty.
Failure of Indoor Unit PCB
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...