5-18
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
26
CC
Not Prepared
-
-
Not Used (Use as 00 conditions)
27
Cd
Not Prepared
-
-
Not Used (Use as 00 conditions)
28
CE
Not Prepared
-
-
Not Used (Use as 00 conditions)
29
CF Change of Louver Swing Angle
○
00
01
02
Standard (7-Step Operation)
Cold Draft Prevention
(5 Steps: lower 2 steps cut off)
High Ceiling (higher 2 steps cut off)
30
d1
Power Supply ON/OFF 1
○
00
01
Not Available
Available
31
d2
Not Prepared
-
-
Not Used
32
d3
Power Supply ON/OFF 2
○
00
01
Not Available
Available
33
d4
Prevention for Cooling Discharge Air
Temp. Decrease
○
00
01
Not Available
Available
34
d5
Prevention for Heating
Discharge Air Temp.
Decrease
Ducted
High
-
-
Not Used
Ducted
Medium
Slim
○
00
01
Not Available
Available
35
d6
Not Prepared
-
-
Not Used (Use as 00 conditions)
36
d7
Not Prepared
-
-
Not Used
37
E1 Not Prepared
-
-
Not Used (Use as 00 conditions)
38
E2 Not Prepared
-
-
Not Used (Use as 00 conditions)
39
E3 Not Prepared
-
-
Not Used (Use as 00 conditions)
40
E4 Not Prepared
-
-
Not Used (Use as 00 conditions)
41
E5 Not Prepared
-
-
Not Used (Use as 00 conditions)
42
E6
Indoor Fan Operation Time After
Cooling Operation Stoppage
○
00
01
02
Not Available
60 min.
120 min.
43
E7 Not Prepared
-
-
Not Used (Use as 00 conditions)
44
E8
Fan Operation Control during
Heating Thermo-OFF
○
00
01
Not Available (LOW)
SLOW
45
E9 Not Prepared
-
-
Not Used (Use as 00 conditions)
46
EA Not Prepared
-
-
Not Used (Use as 00 conditions)
47
Eb Fan Operation Control during
Cooling Thermo-OFF
○
00
01
02
Not Available
LOW
SLOW
48
EC Forced Thermo-ON Stoppage during
Cooling
○
00
01
Not Available
Available
49
Ed Not Prepared
-
-
Not Used (Use as 00 conditions)
50
EE Not Prepared
-
-
Not Used (Use as 00 conditions)
51
EF
Automatic Fan Speed
Control (High 2)
Ducted
High
-
-
Not Used
Ducted
Medium
Slim
○
00
01
Not Available
Available
52
F0 Not Prepared
-
-
Not Used
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...