5-36
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(120) Ambient Temperature Restriction Setpoint Compensation (for Auxiliary Heater Setting) (q5)
This function is utilized to change the outdoor ambient temperature condition to change operation from
auxiliary heater only to Thermo-ON with auxiliary heater.
This function is invalid when the function of "Auxiliary Heater Setting" is invalid.
Setting Condition
Actual Control Temperature
00 (Standard)
(q4) + 4
o
F (2.5
o
C)
01
(q4) + 5
o
F (3.0
o
C)
02
(q4) + 6
o
F (3.5
o
C)
03
(q4) + 1
o
F (0.5
o
C)
04
(q4) + 2
o
F (1.0
o
C)
05
(q4) + 3
o
F (1.5
o
C)
06
(q4) + 3
o
F (2.0
o
C)
(121) Not Prepared (q6)
(122) Not Prepared (q7)
(123) Not Prepared (q8)
(124) Not Prepared (q9)
(125) Not Prepared (qA)
(126) Not Prepared (qb)
(127) Not Prepared (qC)
(128) Not Prepared (qd)
(129) Dual Setpoint (for Automatic COOL/HEAT Operation) (r1)
This function is utilized to activate/deactivate dual setpoint of cooling and heating in automatic cooling
and heating operation.
This function is invalid when the function of "Automatic COOL/HEAT Operation" is invalid.
(130) Cooling/Heating Changeover Temperature (for Automatic COOL/HEAT Operation) (r2)
This function is utilized to change the indoor temperature condition to Thermo-ON/OFF.
This function is invalid when the function of "Dual Setpoint" is invalid.
In case dual setpoint is selected in automatic heating/cooling operation, during auto mode both cooling
setpoint and heating setpoint can be selected.
By default, temperature when the heating/cooling mode changes are as follows.
Cooling mode changes to heating mode when the indoor temperature is heating setpoint -2
o
F (-1
o
C).
Heating mode changes to cooling mode when the indoor temperature is cooling se2
o
F (+1
o
C).
Setting Condition
Actual Control Temperature
00 (Standard)
2
o
F (1.0
o
C)
01
3
o
F (1.5
o
C)
02
3
o
F (2.0
o
C)
03
4
o
F (2.5
o
C)
04
5
o
F (3.0
o
C)
05
1
o
F (0.5
o
C)
NOTE:
Be sure to use only the "00" setting condition when combining this "q5" function with a water source
unit.
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...