5-32
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(64) Cooling Lower Limit for Setting Temperature (FC)
This function is utilized to limit the lowest setting temperature for FAN/COOL/DRY operations.
When this function is valid, it provides the appropriate cooling operation and energy saving.
The setting conditions and the minimum setting temperature for cooling are as follows:
<Example>
(65) Heating Upper Limit for Setting Temperature (Fd)
This function is utilized to limit the highest setting temperature for HEAT operation.
When this function is valid, it provides the appropriate heating operation and energy saving.
The setting conditions and the heating upper limit for the setting temperature are as follows:
<Example>
Setting Condition
Details
Minimum Setting Temperature
(FAN/COOL/DRY) *
00
Standard Value
66
o
F (19
o
C)
01
Lower Limit +2
o
F (Lower Limit +1
o
C)
68
o
F (20
o
C)
02
Lower Limit +4
o
F (Lower Limit +2
o
C)
70
o
F (21
o
C)
03
Lower Limit +6
o
F (Lower Limit +3
o
C)
72
o
F (22
o
C)
04
Lower Limit +8
o
F (Lower Limit +4
o
C)
74
o
F (23
o
C)
05
Lower Limit +10
o
F (Lower Limit +5
o
C)
76
o
F (24
o
C)
06
Lower Limit +11
o
F (Lower Limit +6
o
C)
77
o
F (25
o
C)
07
Lower Limit +12
o
F (Lower Limit +7
o
C)
78
o
F (26
o
C)
08
Lower Limit +14
o
F (Lower Limit +8
o
C)
80
o
F (27
o
C)
09
Lower Limit +16
o
F (Lower Limit +9
o
C)
82
o
F (28
o
C)
10
Lower Limit +18
o
F (Lower Limit +10
o
C)
84
o
F (29
o
C)
* In case of Standard Unit
Setting Condition
Details
Setting Temperature Upper Limit
(HEAT) *
00
Standard Value
86
o
F (30
o
C)
01
Upper Limit -2
o
F (Upper Limit -1
o
C)
84
o
F (29
o
C)
02
Upper Limit -4
o
F (Upper Limit -2
o
C)
82
o
F (28
o
C)
03
Upper Limit -6
o
F (Upper Limit -3
o
C)
80
o
F (27
o
C)
04
Upper Limit -8
o
F (Upper Limit -4
o
C)
78
o
F (26
o
C)
05
Upper Limit -9
o
F (Upper Limit -5
o
C)
77
o
F (25
o
C)
06
Upper Limit -10
o
F (Upper Limit -6
o
C)
76
o
F (24
o
C)
07
Upper Limit -12
o
F (Upper Limit -7
o
C)
74
o
F (23
o
C)
08
Upper Limit -14
o
F (Upper Limit -8
o
C)
72
o
F (22
o
C)
09
Upper Limit -16
o
F (Upper Limit -9
o
C)
70
o
F (21
o
C)
10
Upper Limit -18
o
F (Upper Limit -10
o
C)
68
o
F (20
o
C)
11
Upper Limit -20
o
F (Upper Limit -11
o
C)
66
o
F (19
o
C)
12
Upper Limit -22
o
F (Upper Limit -12
o
C)
64
o
F (18
o
C)
* In case of Standard Unit
Factory-Setting: "00"
(Lower Limit 66+0=66
o
F (19+0=19
o
C))
Setting Condition: "06"
(Lower Limit 66+11=77
o
F (19+6=25
o
C))
66
o
F
(19
o
C)
86
o
F
(30
o
C)
86
o
F
(30
o
C)
77
o
F
(25
o
C)
Temperature Setting: Available
Setting Temperature at Wired Controller
Temperature Setting
: Not Available
Temperature Setting
: Available
Factory-Setting: "00"
(Upper Limit 86-0=86
o
F (30-0=30
o
C))
Setting Condition: "09"
(Upper Limit 86-16=70
o
F (30-9=21
o
C))
64
o
F
(18
o
C)
86
o
F
(30
o
C)
64
o
F
(18
o
C)
70
o
F
(21
o
C)
Setting Temperature at Wired Controller
Temperature Setting: Available
Temperature Setting
: Not Available
Temperature Setting
: Available
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...