SM-18001-rev.1
5-27
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(35) Not Prepared (d6)
(36) Not Prepared (d7)
(37) Not Prepared (E1)
(38) Not Prepared (E2)
(39) Not Prepared (E3)
(40) Not Prepared (E4)
(41) Not Prepared (E5)
(42) Indoor Fan Operation Time After Cooling Operation Stoppage (E6)
This function is utilized to prevent condensation upon cooling operation stoppage by setting “SLOW”
indoor fan operation to dry. “SLOW” operation (for 60 minutes or 120 minutes by setting) continues
even when the cooling operation is stopped.
(43) Not Prepared (E7)
(44) Fan Operation Control during Heating Thermo-OFF (E8)
This function is utilized to prevent the perception of cold draft by reducing the indoor fan speed during
heating Thermo-OFF.
(32) Power Supply ON/OFF 2 (Restarting Function After Power Failure) (d3)
This function is utilized to restart the unit operation automatically when the power supply is restored
after a power failure of over 2 seconds. In case of power failure for 2 seconds or less, the standard
unit retains all the operational functions and restarts the operation automatically. (The compressor
restarts operation after 3 minutes guard in addition to power failure time for up to 2 seconds.)
When this function is utilized in the condition that there is no person to operate the unit, monitor the
system for potential unit failure.
NOTES:
1. If power failure occurs during the stoppage of the unit, the unit remains stopped after the power
supply is restored.
2. When the compressor does not reach the fixed temperature, the system may not restart
automatically after turning on the power supply by hot-start control.
*Hot-start Control: The control program that does not operate the compressor even after the
power is turned ON if the compressor does not reach the fixed temperature.
(33) Prevention for Cooling Discharge Air Temperature Decrease (d4)
This function is utilized to prevent discharge air temperature decrease during the cooling operation by
controlling Thermo-ON/OFF according to the discharge air temperature.
● Thermo-ON:
COOL/DRY operations continue for 3 minutes when discharge air temperature at 52
o
F (11
o
C) or lower.
● Thermo-OFF:
The room temperature reaches the setting temperature when discharge air temperature at 56
o
F (13
o
C)
or higher.
(34) Not Prepared (d5)
...(for Ducted High Static Type)
(34) Prevention for Heating Discharge Air Temperature Decrease (d5)
...(for Ducted Medium Static and
Slim Type)
This function is utilized to prevent discharge air temperature decrease during the heating operation by
making the actual fan speed lower than the speed indicated on the wired controller.
NOTE:
The above table shows when the optional function setting “Hi Speed” is set as standard (00) by the
wired controller.
Large
Fan Speed
Small
Indications on
Wired Controller
HIGH2
HIGH
MED
LOW
Actual Fan Speed
HIGH
HIGH
LOW
LOW
Setting Condition
Fan Operation
during
Thermo-OFF
00
LOW
01
SLOW
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...