TROUBLESHOOTING
Check the following items if there is any abnormality in the activation of the system.
No.
Check Situation
Check Method
1 Is any power supply breaker or
fuse open?
Check the voltage (secondary side) of the breaker and also
check the continuity of the fuse with a tester.
2 Is voltage at the secondary side
of the transformer correct?
Disconnect at the secondary side of the transformer and measure
voltage with a tester.
3
Is wiring firmly secured and
correctly connected?
Check that the following wiring connection on O.U./I.U. printed circuit
boards (PCBs) is not loose.
• The connection for thermistors
• The connection for the wired controller cable
• The connection for communication cabling
• Each connection for power supply line
Check that the wiring connection on O.U./I.U. PCBs is not loose or
misconnected on the site according to the “Electrical Wiring Diagram” of
the Engineering Manual.
NOTE:
If the fuse(s) on an I.U. PCB is blown, diagnose the cause of overcurrent and replace the fuse(s).
In addition, check the power supply of optional equipment because the fuse(s) may blow due to an external
power supply failure. Turn off the power for safety.
3.1 Initial Troubleshooting
3.1.1 Checking Electrical Wiring and Power Supply
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...