5-28
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(48) Forced Thermo-ON Stoppage during Cooling (EC)
This function is utilized to force Thermo-ON and then stop the operation when cooling operation is
stopped.
This is effective to prevent abnormal odor because the heat exchanger is rinsed with drain water to
keep in the clean condition.
(49) Not Prepared (Ed)
(50) Not Prepared (EE)
(51) Not Prepared (EF)
...(for Ducted High Static Type)
(51) Automatic Fan Speed Control (Corresponding to HIGH2)(EF)
...(for Ducted Medium Static and
Slim Type)
This function is utilized to increase the maximum fan speed to "HIGH2" setting condition when the
maximum fan speed remain "HIGH" by default.
The fan speed setting (EF) by Wired Controller are shown below.
(45) Not Prepared (E9)
(46) Not Prepared (EA)
(47) Fan Operation Control during Cooling Thermo-OFF (Eb)
This function is utilized to prevent diffusion of odor and high humidity by reducing the indoor fan speed
during cooling Thermo-OFF.
Setting Condition
Fan Operation
during
Thermo-OFF
00
Operation at Set Fan Speed
01
LOW
02
SLOW
Function
Selection
EF Setting
Wired Controller Setting
AUTO
HIGH2
HIGH
MED
LOW
00
HIGH - LOW
HIGH2
HIGH
MED
LOW
01
HIGH2 - LOW
HIGH2
HIGH
MED
LOW
NOTE:
This function is not available when the auxiliary heater is enabled. Fan speed is either "HIGH" or
"HIGH2" during this time.
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...