4.2.2.7 Removing Condensate Pump
The condensate pump is mounted on the service cover. Remove the service cover according to Section
4.2.2.4 (1) “Removing Thermistors for Liquid Pipe and Gas Pipe”.
Remove the securing screws and remove the condensate pump.
Phillips Screwdriver, Wrench
Tool
Indoor Unit
Condensate Connection
Service Cover
A
A
View from
Condensate Pan
Condensate Pump
TURN OFF all POWER supply switches.