5-34
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Setting Condition
Thermistor (Sensor)
00
Inlet Air Thermistor
01
Outlet Air Thermistor
02
Thermistor of Remote Control
03
Remote Sensor
(95) Not Prepared (L3)
(96) Not Prepared (L4)
...(for Ducted High Static Type)
(96) Fan Speed during Energy-Saving Forced Thermo-OFF (L4)
...(for Ducted Medium Static and
Slim Type)
This function is utilized to increase the fan speed to prevent the deterioration of comfort due to force
thermo-OFF for energy saving during cooling operation.
(97) Not Prepared (L5)
(98) Not Prepared (L6)
(99) Not Prepared (L7)
(100) Not Prepared (L8)
(101) Auxiliary Heater OFF at Defrost Operation (L9)
This function is utilized to activate/deactivate heater during defrost operation when heater operation is
enabled.
The setting conditions and the heater during defrost are as follows:
(102) Not Prepared (LA)
(103) Not Prepared (Lb)
(104) Setting Temperature (P1)
This function is utilized to provide setting temperature for every 1
o
F (0.5
o
C) at "00" and every 2
o
F (1
o
C)
at "01".
Control differential of thermistor also take the temperature for every 1
o
F (0.5
o
C) at "00" and every 2
o
F
(1
o
C) at "01".
(105) Not Prepared (P2)
(106) Thermistor Selection (P3)
This function is utilized to select the thermistor with function (107).
Setting Condition
Air Volume During Force Thermo-OFF
Airflow Volume
HIGH2
HIGH
MED
LOW
00 (Standard)
HIGH2
HIGH
MED
LOW
01 (Hi Speed)
HIGH2
HIGH2
HIGH
MED
(107) Display of Thermistor Temperature (P4)
This function is utilized to display the temperature of the sensor selected at (106).
(108) Setting Temperature Display during Fan Operation (P5)
This function is utilized to undisplay the setting temperature during fan mode operation.
(109) ECO Button Operation (P6)
This function is prohibiting "ECO" button operation by setting at "01"
(110) Menu Button Operation (P7)
This function is utilized to invalidate the menu button.
(111) Not Prepared (P8)
(112) Not Prepared (P9)
(113) Not Prepared (PA)
(114) Not Prepared (Pb)
(115) Not Prepared (PC)
Setting Condition
Heater during Defrost
Fan Operation
00
ON
SLOW
01
OFF
STOP
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...