SM-18001-rev.1
3-29
TROUBLESHOOTING
Alarm
Code
Abnormality of Thermistor for Gas Refrigerant Pipe Temperature
at Indoor Unit Heat Exchanger (Gas Pipe Thermistor)
l
The RUN indicator (red) flashes.
l
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code
1
,
the model name
1
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
Note 1: Except for some models.
This alarm code is displayed when a short (0.24kΩ or less) or open sensor (840kΩ or more) is detected
during a heating or cooling operation. The operation automatically restarts when the malfunction is
removed.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Failure of
Thermistor
for Indoor Unit
Heat Exchanger
Gas Pipe Temp.
Check resistance.
Replace thermistor
if faulty.
Failure
Check wiring to
I.U. PCB.
Correctly connect wires.
Incorrect Connection
Replace I.U. PCB
and check operation.
Replace I.U. PCB
if faulty.
Failure of I.U. PCB
1: The heating operation is available only during the test run.
● High Static Type: (H,Y)IDH018 to 048B21S
● Medium Static Type: (H,Y,C)IDM006 to 048B21S
● Slim Type: (H,Y,C)IDS006 to 018B21S
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Refer to "Alarm Code 11"
for thermistor resistance.
Yes
Yes
Connect them.
No
Failure of
Thermistor
Failure of I.U. PCB
No
Is thermistor THM5
(for gas pipe) connected
to THM5 of I.U. PCB?
Is resistance of THM5
between 0.24k
Ω
and
840k
Ω
?
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...