TROUBLESHOOTING
3.2.1 Alarm Code Table
Code
Category
Content of Abnormality
Leading Cause
01
Indoor Unit
Activation of Protection Device
(Float Switch)
Activation of Float Switch (High Water Level in
Condensate Pan, Problem with Condensate Piping,
Float Switch, or Condensate Pan)
03
Communication Operational Irregularities between
Indoor and Outdoor
Incorrect Wiring, Loose Terminals, Disconnect Wire,
Blowout of Fuse, Outdoor Unit Power OFF
11
Sensor on
Indoor Unit
Inlet Air Thermistor
Incorrect Wiring, Disconnecting Wiring
Breaking Wire, Short Circuit
12
Outlet Air Thermistor
13
Freeze Protection Thermistor
14
Gas Piping Thermistor
19
Fan Motor
Activation of Protection Device for
Indoor Fan
Fan Motor Overheat, Lockup
31
System
Incorrect Capacity Setting of
Outdoor Unit and Indoor Unit
Incorrect Capacity Code Setting of Combination
Excessive or Insufficient Indoor Unit Total
Capacity Code
35
Incorrect Setting of Indoor Unit No. Duplication of Indoor Unit No. in same Refrigerant
Group
b0
Incorrect Setting of Unit Model
Code
Unit model code setting is not set or is set for the
incorrect indoor unit type.
b1
Incorrect Setting of Unit and
Refrigerant Cycle Number
There are 64 or More Number is Set for Address or
Refrigerant Cycle.
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...