(Cleaning Indoor Unit Heat Exchanger)
MAINTENANCE
4-42
SM-18001-rev.1
Step
Procedure
Required Tool
8
Cleaning with Clean Water
Nozzle
Spray
Pump
Hose
Bucket
* Water Tank
* Pump
* Washer
Insert the nozzle into the hole of the cleaning water
collector. Operate the pump, wash the dust off on
the fins with clean water thoroughly. If the cleaning
agent is left on the fins, it may cause corrosion.
Adjust the pressure of the spray at approximately 36
to 71 psi (2.5 to 5.0 kg/cm
2
) so as not to crush the
fins and direct the nozzle in a straight line toward the
fins.
9
Make sure that there are no drops of water left after cleaning the fins and
reassemble the fan assembly and the condensate pan.
* Screwdriver
* Hexagon Wrench
10
Measure the condition of insulation of the condensate pump with a megohm-
meter tester. (Check to ensure that the resistance is bigger than 1 MΩ at 500V.)
11
Connect the electrical wiring as it was and attach the removed parts.
* Screwdriver
12
Neutralization Treatment after Cleaning
The cleaning agent specified in Section 4.3.1, is of neutral type.
However, the cleaning water after cleaning may be not neutral due to dust or other
foreign particles. Collect all cleaning water and make necessary neutralization for
the cleaning water.
Summary of Contents for CIDH018B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...