Note
・
If the input type is changed, the max./min. value of input range, max./min. value of
input scale, and input scale decimal point position will be initialized.
・
Configure settings in the following order: max. value of input range, min. value of
input range, max. value of input scale, and then min. value of input scale.
・
If using a thermocouple or resistance temperature detector, do not change the max.
value of input scale, min. value of input scale, or decimal point position.
Table 5. Analog input setting parameters (channel 1 (CH1))
Register number
(Reference no.)
Hex number
(hexadecimal)
Register name
R/W
Descriptions
41501
05DC
CH1 tag
R/W
Set using UTF16.
41502
05DD
R/W
41503
05DE
R/W
41504
05DF
R/W
41505
05E0
R/W
41506
05E1
R/W
41507
05E2
R/W
41508
05E3
R/W
41509
05E4
R/W
41510
05E5
R/W
41511
05E6
R/W
41512
05E7
R/W
41513
05E8
R/W
41514
05E9
R/W
41515
05EA
R/W
41516
05EB
R/W
41517
05EC
R/W
41518
05ED
CH1 input type
R/W
0: SKIP
1: 20 mV
2: 60 mV
3: 200 mV
4: 1 V
5: 2 V
6: 6 V
7: 10 V
8: 20 V
9: 50 V
10: 0.4 to 2 V
11: 1 to 5 V
14: 200
Ω
4-wire
15: 2000Ω 4
-wire
16: Type R
17: Type S
18: Type B
19: Type K
21: Type E
22: Type J
23: Type T
24: Type N
25: Type C
26: Pt100 3-wire
27: Pt100-H 3-wire
28: Pt100 4-wire
29: Pt100-H 4-wire
Summary of Contents for VZ20X
Page 16: ...Contents 3 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Revision Information 1...
Page 17: ...Contents 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 23: ...2 2 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 29: ...3 6 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 145: ...9 10 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 149: ...App 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...