7-23
IM 77V01B01-01EN
5th Edition: 2023.03.07-00
Table 2. Reading of measured values and statuses by individual channel
Register number
(Reference no.)
Hex number
(hexadecimal)
Register name
R/W
Descriptions
40151
0096
Measured value time stamp
R The time of measured values can
be read.
This setting is common to all
channels.
The coordinated universal time or
UTC can be read as a 64-bit
unsigned integer.
40152
0097
R
40153
0098
R
40154
0099
R
40155
009A
Device status
R The device status of the VZ20X
can be read.
40156
009B
CH1 measured value
R Measured values can be read as
32-bit signed integers.
The range changes depending on
the input range.
40157
009C
R
40158
009D
CH1 measured value status
R The status of measured values
can be read.
40159
009E
CH2 measured value
R
Same as CH1 measured value
40160
009F
R
40161
00A0
CH2 measured value status
R Same as CH1 measured value
status
40162
00A1
CH3 measured value
R
Same as CH1 measured value
40163
00A2
R
40164
00A3
CH3 measured value status
R Same as CH1 measured value
status
40165
00A4
CH4 measured value
R
Same as CH1 measured value
40166
00A5
R
40167
00A6
CH4 measured value status
R Same as CH1 measured value
status
40168
00A7
CH5 measured value
R
Same as CH1 measured value
40169
00A8
R
40170
00A9
CH5 measured value status
R Same as CH1 measured value
status
40171
00AA
CH6 measured value
R
Same as CH1 measured value
40172
00AB
R
40173
00AC
CH6 measured value status
R Same as CH1 measured value
status
40174
00AD
CH7 measured value
R
Same as CH1 measured value
40175
00AE
R
40176
00AD
CH7 measured value status
R Same as CH1 measured value
status
40177
00B0
CH8 measured value
R
Same as CH1 measured value
40178
00B1
R
40179
00B2
CH8 measured value status
R Same as CH1 measured value
status
Reading of values appended with decimal point
When values with decimal points are read from a host device, values (hexadecimal)
after removal of the decimal point can be read.
Example: When the measured value "12.3" is read from the host device, the value "123"
after removal of the decimal point (same applies to value "1.23", "123 is read) is
converted to hexadecimal. Therefore, "7B" can be read.
In this case, the register for the decimal point position is "Decimal position (n=1 to 8) of
CHn measured value" and the register numbers are 40301 to 40308.
In the case of measured value "1.23": Decimal point position of measured value = 2
Summary of Contents for VZ20X
Page 16: ...Contents 3 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Revision Information 1...
Page 17: ...Contents 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 23: ...2 2 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 29: ...3 6 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 145: ...9 10 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 149: ...App 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...