7-37
IM 77V01B01-01EN
5th Edition: 2023.03.07-00
●
Network frame configuration
The Modbus/TCP frame configuration is as follows.
MBAP Header (Modbus Application Protocol Header): Header for identifying that the
protocol is Modbus/TCP
PDU (Protocol Data Unit): Body of data communication
●
MBAP Header configuration
The MBAP Header comprises the following seven bytes.
Byte No.
0
1
2
3
4
5
6
Description
Transfer ID
Protocol ID
Number of bytes
Unit ID
Transfer ID: Specify any value for identifying transactions on the host device. The
VZ20X returns the value received from a PC/PLC as the response.
Protocol ID: Specify "0" in the case of the Modbus/TCP protocol.
Number of bytes: The number of bytes from the unit ID (byte No.6) onwards.
Unit ID: Specify "1" on the host device. "1" is returned from the VZ20X, too, as the
response.
MODBUS TCP/IP ADU
PDU
MBAP Header
Function code
Data