App-2
IM 77V01B01-01EN
5th Edition: 2023.03.07-00
Setting > Time Synchronization
Parameter Name
Setting Range
Default
Explanation
Connection
type
(*1)
1 unit
Master unit of daisy chain
Relay unit of daisy chain
Terminal unit of daisy chain
1 unit
This sets the connection method
between the PC and the VZ20X.
*1: Communication is turned off, and these parameters require beginning with a new connection when setting values
were changed in a USB connection.
Setting > Analog Input
Parameter Name
Setting Range
Default
Explanation
CH tag
Max. 16, 2- or 1-bytes
characters
(alphanumeric characters,
symbols and Chinese
character)
CHn
n=1 to 8
This sets the tag name of channel.
Input type
See table of input type.
(Sub section 7.1.1)
OFF
This sets input type.
Temperature Unit Fixed to °C
°C
The temperature unit is used for
thermocouples and resistance
temperature detectors.
Max. value of input
range
According to input type
Min. value of input range <
Max. value of input range
Min. value of input range +
1 digit to upper limit value
of measurement range
The default follows
the upper limit value
of each input type in
the input type table.
This sets the maximum
measurement value of the input.
Min. value of input
range
According to input type
Min. value of input range <
Max. value of input range
Lower limit value of
measurement range to
max. value of input range -
1 digit
The default follows
the lower limit value
of each input type in
the input type table.
This sets the minimum
measurement value of the input.
Max. value of input
scale
-99999 to 99999
Min. value of input scale <
Max. value of input scale
Min. value of input scale +
1 digit to 99999
The default follows
the upper limit value
of each input type in
the input type table.
This sets the maximum value to be
used in scaling calculation.
Min. value of input
scale
-99999 to 99999
Min. value of input scale <
Max. value of input scale
-99999 to max. value of
input scale - 1 digit
The default follows
the lower limit value
of each input type in
the input type table.
This sets the minimum value to be
used in scaling calculation.
Input scale decimal
point position
0 to 4
The default follows
the decimal point
position of the input
scale the input type
table.
This sets the decimal point
position after scaling.
Burnout detection OFF, UP, DOWN
UP
This parameter is for setting
burnout detection.
Power supply
frequency noise
removal filter
OFF, ON
OFF
This toggles the power frequency
noise removal filter setting between
disabled/enabled.
Power supply
frequency noise
removal setting
50 Hz, 60 Hz, COMMON 50 Hz
Set the power frequency noise
removal filter.
50 Hz: Filters out 50 Hz noise.
60 Hz: Filters out 60 Hz noise.
COMMON: Filters out noise both 50
Hz and 60 Hz.
Data acquisition
interval
1 ms, 10 ms, 50 ms,
100 ms
1 ms
Input value can be acquired at a set
interval and used as a measured
value.
Moving average
filter
OFF, ON
OFF
This toggles the moving average
filter setting between use/non-use.
Number of moving
average cycles
2 to 100
100
Set the number of times in which the
moving average is calculated.
Summary of Contents for VZ20X
Page 16: ...Contents 3 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Revision Information 1...
Page 17: ...Contents 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 23: ...2 2 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 29: ...3 6 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 145: ...9 10 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Page 149: ...App 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...