4 Setting Up with the Main Unit
49
49
Preparing f
o
r
Measurement
■
Batch-setting the alarm function
The following procedure is used to set the
same alarm function for all tags.
Home screen
18:54:27
222
222
25.9
°
C
1.
Press the [FUNC], [7], and [1] keys, in
order.
The “All File” screen appears on the LCD.
F71
A l l
F i l e
2.
Press the [SET] key.
A screen for setting the “Hi Alarm” function ON/OFF
appears.
Hi Alarm
ON
3.
Use either the [
▼
] or [
▲
] key to set the
upper-limit temperature alarm function
ON/OFF.
4.
If ON has been selected, press the [SET]
key.
The “Hi Alarm” setting screen appears.
If OFF has been selected in step 3, this screen will
not appear. In this case proceed to step 6.
Hi Alarm
0 0 0 0 . 0
°
C
5.
Enter the upper-limit temperature.
Hi Alarm
0 0 2 0 . 0
°
C
[TIP]
To set a negative value, press either the [
▼
] or
[
▲
] key. “0” on the screen will change to a
“-” symbol.
6.
Press the [SET] key.
The specified upper-limit temperature is set and the
screen of selecting ON/OFF of the “Lo Alarm” func-
tion appears.
Lo Alarm
ON
7.
Use either the [
▼
] or [
▲
] key to select
ON/OFF of the lower-limit temperature
alarm function.
8.
When ON has been selected, press the
[SET] key.
The “Lo Alarm” setting screen appears.
If OFF has been selected in step 7, this screen will
not appear. In this case proceed to step 10.
Lo Alarm
0 0 0 0 . 0
°
C