CAUTION!
Please regard that the voltage applied to an output channel must be
£
the
voltage supply applied to L+. Due to the parallel connection of in- and
output channel per group, a set output channel may be supplied via an
applied input signal. Thus, a set output remains active even at power-off
of the voltage supply with the applied input signal. Non-observance may
cause module demolition.
Pin assignment Circuit diagram Status monitor
Pin
Assignment
Circuit diagram
LED
Description
1
Not used
1L+,
2L+
LED (green)
supply voltage is on
2
Input
I+0.0
.0
...
.7
LED (green)
I+0.0 ... I+1.7
Q+0.0 ... Q+1.7
At signal "1" (input)
res. active output, the
according LED is acti-
vated
...
...
F
LED (red)
error at overload, short
circuit
19
Input
I+1.7
20
Ground 1M
inputs
21, 31 Supply voltage
DC +24V
22
Output
Q+0.0
...
...
39
Output
Q+1.7
30
Ground 2M
outputs
40
Ground 3M
outputs