Order no.
322-5FF00
Rated load voltage
AC 120/230 V
Current consumption from load voltage L+ (without load)
2 mA
Total current per group, horizontal configuration, 40°C
8 A
Total current per group, horizontal configuration, 60°C
4 A
Total current per group, vertical configuration
4 A
Output current at signal "1", rated value
2 A
Output delay of "0" to "1"
-
Output delay of "1" to "0"
-
Minimum load current
-
Lamp load
50 W
Parallel switching of outputs for redundant control of a load possible
Parallel switching of outputs for increased power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 10 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 1 Hz
Internal limitation of inductive shut-off voltage
-
Short-circuit protection of output
Fuse 3.15 A /250 V, quick response
Trigger level
3.15 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
1 Byte
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Supply voltage display
none
Group error display
red SF LED
Channel error display
none
Isolation
Between channels
ü
Between channels of groups to
1
Between channels and backplane bus
ü
VIPA System 300S
Digital Output Modules
322-5FF00 - DO 8xAC 120/230V 2A > Technical data
HB140 | SM-DIO | | en | Rev. 16-43
64