Order no.
323-1BH00
Output delay of "0" to "1"
150 µs
Output delay of "1" to "0"
100 µs
Minimum load current
-
Lamp load
5 W
Parallel switching of outputs for redundant control of a load possible (only outputs group)
Parallel switching of outputs for increased power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 1000 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 Hz
Internal limitation of inductive shut-off voltage
L+ (-52 V)
Short-circuit protection of output
yes, electronic
Trigger level
1.5 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
2 Byte
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Supply voltage display
green LED per group
Group error display
red SF LED
Channel error display
none
Isolation
Between channels
ü
Between channels of groups to
8
Between channels and backplane bus
ü
Insulation tested with
DC 500 V
Datasizes
Input bytes
2
Output bytes
2
Parameter bytes
0
Diagnostic bytes
0
VIPA System 300S
Digital Input/Output Modules
323-1BH00 - DIO 16xDC 24V 1A > Technical data
HB140 | SM-DIO | | en | Rev. 16-43
74