Order no.
322-1BF01
Technical data digital outputs
Number of outputs
8
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Current consumption from load voltage L+ (without load)
68 mA
Total current per group, horizontal configuration, 40°C
8 A
Total current per group, horizontal configuration, 60°C
8 A
Total current per group, vertical configuration
8 A
Output current at signal "1", rated value
2 A
Output delay of "0" to "1"
150 µs
Output delay of "1" to "0"
100 µs
Minimum load current
-
Lamp load
10 W
Parallel switching of outputs for redundant control of a load possible (only outputs group)
Parallel switching of outputs for increased power
possible (only outputs group)
Actuation of digital input
ü
Switching frequency with resistive load
max. 1000 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 Hz
Internal limitation of inductive shut-off voltage
L+ (-52 V)
Short-circuit protection of output
yes, electronic
Trigger level
3 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
1 Byte
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Supply voltage display
green LED per group
Group error display
red SF LED
Channel error display
none
VIPA System 300S
Digital Output Modules
322-1BF01 - DO 8xDC 24V 2A > Technical data
HB140 | SM-DIO | | en | Rev. 16-43
40