Via this record set you may activate a process interrupt for I+0.0 ... I+1.7 and define for
which edge of the input signal a process interrupt is thrown.
The record set has the following structure:
Byte
Bit 7 ... Bit 0
0
n
Bit 1, 0: Edge selection I+0.0
–
00b = de-activated
–
01b = Process interrupt at ascending edge
–
10b = Process interrupt at descending edge
–
11b = Process interrupt at both edges
n
Bit 7 ... 2: reserved
...
...
15
n
Bit 1, 0: Edge selection I+1.7
–
00b = de-activated
–
01b = Process interrupt at ascending edge
–
10b = Process interrupt at descending edge
–
11b = Process interrupt both edges
n
Bit 7 ... 2: reserved
Every SPEED-Bus module carries along a timer with a resolution of 1µs. The timer starts
at boot-up of the CPU. Thus gives you a time base with an accuracy of ±1µs at the
SPEED-Bus. By parameterization of the ETS function (
E
dge
T
ime
s
tamp) for an input, the
current time value is entered in the process image of the module at according edge. Thus
allows you to compare times of different input channels via your user application.
Via the parameter
Time stamp
you may activate the ETS system and define the edge of
the input signal that initiates the process image entry of a time stamp. You have the fol-
lowing options:
n
No time stamp
n
Time stamp at ascending edge
n
Time stamp at descending edge
n
Time stamp at both edges
Allocation in the process image
Ä
‘48bytes in the process image’ on page 111
The stored times correspond the point in time when the signal has
already passed the input filter of the module. To calculate the real time at
the clamp, you have to subtract the delay time of 1µs and the parameter-
ized delay time defined under Filter.
Record set 80h Edge
selection (Byte 0 ... 15)
Record set 80h ETS Time
stamp (Byte 16 ... 31)
VIPA System 300S
Digital Modules FAST - SPEED-Bus
323-1BH70 - DIO 16xDC 24V 0.5A > Parameterization
HB140 | SM-DIO | | en | Rev. 16-43
110