11.11 o: Keypad-Related Settings
264
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o3-05
(0BDA)
Select Items to Backup/
Restore
Sets which parameters are backed up, restored, and referenced. This parameter is only
available when using an LCD keypad.
0 : Standard Parameters
1 : St DWEZ Parameters
0
(0, 1)
o3-06
(0BDE)
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only
available when using an LCD keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o3-07
(0BDF)
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters
from the drive to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
1
(0 - 3)
◆
o4: Maintenance Monitor Settings
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o4-01
(050B)
Expert
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
o4-02
(050C)
Expert
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
1
(0, 1)
o4-03
(050E)
Expert
Fan Operation Time
Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-
hour units.
0 h
(0 - 9999 h)
o4-05
(051D)
Expert
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
o4-07
(0523)
Expert
Softcharge Relay
Maintenance Set
Sets the
U4-06 [PreChargeRelayMainte]
monitor value.
0%
(0 - 150%)
o4-09
(0525)
Expert
IGBT Maintenance
Setting
Sets the
U4-07 [IGBT Maintenance]
monitor value.
0%
(0 - 150%)
o4-11
(0510)
Expert
Fault Trace/History Init
(U2/U3)
Resets the records of Monitors
U2-xx [Fault Trace]
and
U3-xx [Fault History]
.
0 : Disabled
1 : Enabled
0
(0, 1)
o4-12
(0512)
Expert
kWh Monitor
Initialization
Resets the monitor values for
U4-10 [kWh, Lower 4 Digits]
and
U4-11 [kWh, Upper 5
Digits]
.
0 : No Reset
1 : Reset
0
(0, 1)
o4-13
(0528)
Expert
RUN Command Counter
@ Initialize
Resets the monitor values for
U4-02 [Num of Run Commands]
,
U4-24 [Number of Runs
(Low)]
, and
U4-25 [Number of Runs (High)]
.
0 : No Reset
1 : Reset
0
(0, 1)
o4-22
(154F)
RUN
Expert
Time Format
Sets the time display format. This parameter is only available when using an LCD
keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
0
(0 - 2)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...