11.11 o: Keypad-Related Settings
262
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
11.11 o: Keypad-Related Settings
◆
o1: Keypad Display
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o1-01
(0500)
RUN
User Monitor Selection
Sets the
U monitor
for the Drive Mode. This parameter is only available with an LED
keypad.
106
(104 - 830)
o1-02
(0501)
RUN
Expert
Monitor Selection at
Power-up
Sets the monitor item that the keypad screen shows after you energize the drive. Refer
to
“
U: Monitors
”
for information about the monitor items that the keypad screen can
show. This parameter is only available with an LED keypad.
1 : Frequency Reference (U1-01)
2 : Direction
3 : Output Frequency (U1-02)
4 : Output Current (U1-03)
5 : User Monitor (
o1-01
)
1
(1 - 5)
o1-03
(0502)
Keypad Display Unit
Selection
Sets the display units for the frequency reference and output frequency.
0 : 0.01 Hz units
1 : 0.01% units
2 : Revolutions Per Minute (RPM)
3 : User Units
0
(0 - 3)
o1-10
(0520)
Expert
User Units Maximum
Value
Sets the value that the drive shows as the maximum output frequency.
Determined by o1-03
(1 - 60000)
o1-11
(0521)
Expert
User Units Decimal
Position
Sets the number of decimal places for frequency reference and monitor values.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Determined by o1-03
(0 - 3)
o1-24 to o1-29:
(11AD - 11B2)
RUN
Custom Monitor 1 to 6
Sets a maximum of 6 monitors as user monitors. This parameter is only available when
using an LCD keypad.
o1-24: 101
o1-25: 102
o1-26: 103
o1-27 to o1-29: 0
(0, 101 - 999)
◆
o2: Keypad Operation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o2-01
(0505)
Expert
LO/RE Key Function
Selection
Sets the function that lets you use
to switch between LOCAL and REMOTE
Modes.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-02
(0506)
Expert
STOP Key Function
Selection
Sets the function to use
on the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-03
(0507)
Expert
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults
to use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
o2-04
(0508)
Expert
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...