12.9 o: Keypad-Related Settings
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
351
Set
o2-03 = 2
then push
to clear the user parameter setting values. The drive will automatically reset
o2-03
to
0
. If you delete the user parameter setting values, you cannot set
A1-03 = 1110
to initialize parameters.
■
o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-04
(0508)
Expert
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
NOTICE:
Set o2-04 [Drive Model (KVA) Selection] correctly. If you set this parameter incorrectly, it will decrease drive
performance, cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of
o2-04
changes, related parameter setting values also change.
lists the relation between
o2-04
setting values and drive models.
Table 12.13 Drive Models and
o2-04
Settings
Drive Model
o2-04 Setting
4009
6E
4015
6F
4018
9A
4024
9C
Drive Model
o2-04 Setting
4031
9D
4039
9E
4045
9F
■
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-05
(0509)
Expert
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push
to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
and
on
the keypad to change the frequency reference value.
■
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name
Description
Default
(Range)
o2-06
(050A)
Expert
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
0
(0, 1)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects
oPr [Keypad Connection Fault]
, and the motor coasts to stop when the drive
detects a keypad disconnection.
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...