6.1 MEMOBUS/Modbus Communications
138
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
Figure 6.4 Wiring Diagram for More than One Drive
Note:
1. Set DIP switch S2 to the ON position on the last drive of the MEMOBUS/Modbus communication network to enable the termination
resistor.
2. For long cable runs or multi-floor installations, connect the shield to ground at only one device on the network (at the PLC, if
possible) to prevent ground loops. When you remove the shield from the ground terminal, it can increase the communication quality
in some drive installation locations.
◆
MEMOBUS/Modbus Drive Operations
Drive parameters will apply to the settings when the drive is running during MEMOBUS/Modbus
communications. This section gives information about the available functions and their related parameters.
■
Executable Functions
A PLC can do these operations with MEMOBUS/Modbus communications. Parameter settings (except
H5-xx
) do
not have an effect on the availability of these operations.
•
Monitor the drive status and operate the drive
•
Set and view parameters
•
Fault Reset
•
Multi-function input settings
The input command from MEMOBUS/Modbus communications and MFDI terminals (S1 to S7) are linked by a
logical OR operation.
■
Drive Control
Select the external command that sets the frequency references and motor run/stop with MEMOBUS/Modbus
communications. Use the information in
to set the parameters as specified by the application.
Table 6.2 Necessary Parameter Settings for Drive Control from MEMOBUS/Modbus
LOCAL Control Selected
No.
Name
Setting Value
External reference 1
b1-01
Frequency Reference Selection 1
2 [Memobus/Modbus Communications]
b1-02
Run Command Selection 1
2 [Memobus/Modbus Communications]
External reference 2
b1-15
Frequency Reference Selection 2
2 [Memobus/Modbus Communications]
b1-16
Run Command Selection 2
2 [Memobus/Modbus Communications]
For more information about operation mode selection, refer to
b1-01 [Frequency Reference Selection 1]
and
b1-02
[Run Command Selection 1]
. Refer to
H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
for
more information about external commands.
◆
Communications Timing
To prevent overrun of the slave side, the master cannot send a message to the same drive for a selected length of
time.
To prevent overrun of the master side, the slave cannot send a response message to the master for a selected length
of time.
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...