246
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
11.7
E: Motor Parameters
◆
E1: V/f Pattern for Motor 1
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
NOTICE:
Damage to Equipment. Set E1-01 [Input AC Supply
Voltage] to align with the drive input voltage (not motor
voltage). If this parameter is incorrect, the protective functions
of the drive will not operate correctly and it can cause damage
to the drive.
400 V: 400 V
(400 V Class: 310 - 510
V)
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02
(10.0 - 120.0 Hz)
E1-05
(0304)
Maximum Output
Voltage
Sets the maximum output voltage for the V/f pattern.
400 V Class: 380.0 V
(400 V Class: 0.0 - 510.0
V)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02
(0.0 - 120.0 Hz)
E1-07
(0306)
Middle Output
Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - 120.0 Hz)
E1-08
(0307)
Middle Output
Frequency Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02
and o2-04
(400 V Class: 0.0 - 510.0
V)
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02
(0.0 - 120.0 Hz)
E1-10
(0309)
Minimum Output
Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by o2-04
(400 V Class: 0.0 - 510.0
V)
E1-11
(030A)
Expert
Middle Output
Frequency 2
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - 120.0 Hz)
E1-12
(030B)
Expert
Middle Output
Frequency Voltage 2
Sets a middle point voltage for the V/f pattern.
0.0 V
(400 V Class: 0.0 - 510.0
V)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(400 V Class: 0.0 - 510.0
V)
◆
E2: Motor Parameters
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E2-01
(030E)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the
drive rated current)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04
(0.00 - 20.00 Hz)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency
and the no-load voltage.
Determined by o2-04
(0 to E2-01)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 48)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
E2-06
(0313)
Motor Leakage
Inductance
Sets the voltage drop from motor leakage inductance when the motor is operating at the
rated frequency and rated current. This value is a percentage of Motor Rated Voltage.
Determined by o2-04
(0.0 - 60.0%)
E2-07
(0314)
Motor Saturation
Coefficient 1
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
0.50
(0.00 - 0.50)
E2-08
(0315)
Motor Saturation
Coefficient 2
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
0.75
(E2-07 - 0.75)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...