300
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
■
E1-08: Middle Output Frequency Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-08
(0307)
Middle Output Frequency
Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02 and
o2-04
(400 V Class: 0.0 - 510.0
V)
Note:
Default setting is determined by
A1-02 [Control Method Selection]
, and
o2-04 [Drive Model Selection]
.
■
E1-09: Minimum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02
(0.0 - 120.0 Hz)
■
E1-10: Minimum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by o2-04
(400 V Class: 0.0 - 510.0
V)
■
E1-11: Middle Output Frequency 2
No.
(Hex.)
Name
Description
Default
(Range)
E1-11
(030A)
Expert
Middle Output Frequency 2
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - 120.0 Hz)
Note:
Set this parameter to
0.0 Hz
to disable the function.
■
E1-12: Middle Output Frequency Voltage 2
No.
(Hex.)
Name
Description
Default
(Range)
E1-12
(030B)
Expert
Middle Output Frequency
Voltage 2
Sets a middle point voltage for the V/f pattern.
0.0 V
(400 V Class: 0.0 - 510.0
V)
Note:
Set this parameter to
0.0 V
to disable the function.
■
E1-13: Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(400 V Class: 0.0 - 510.0
V)
Note:
•
After Auto-Tuning, the value of
E1-13
=
E1-05 [Maximum Output Voltage]
.
•
When
E1-13 = 0.0
, use the value of
E1-05
to control the voltage.
◆
E2: Motor Parameters
E2 parameters [Motor Parameters]
are used to set induction motor data. To switch drive operation from one
motor to another motor, configure the first motor (motor 1).
If Auto-Tuning cannot be performed, set the
E2 parameters
manually. Performing Auto-Tuning automatically sets
the
E2 parameters
to the optimal values.
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...