YASKAWA
SIEPYEULA5001C LA500 Technical Manual
229
◆
Altitude Derating
Install the drive in a location that has an altitude of 1000 m (3281 ft) or lower.
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 to 4000 m
(3281 to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
•
Installing the drive at 2000 m (6562 ft) or lower
•
Installing the drive between 2000 to 4000 m (6562 to 13123 ft) and grounding the neutral point on the power
supply.
If you do not ground the drive with a neutral network, contact Yaskawa or your nearest sales representative.