Fault
This section gives information about some of the causes and possible solutions of faults. You must use the Fault
Reset operation to remove the fault before you can operate the drive. Use the information in this table to remove
the cause of the fault.
Code
Name
Causes
Possible Solutions
bAT
Keypad Battery Low Voltage
The keypad battery voltage is low.
Replace the keypad battery.
Note:
Use
o4-24 [bAT Detection Selection]
to enable/disable
bAT
detection.
Code
Name
Causes
Possible Solutions
bCE
Bluetooth Communication Fault
The smartphone or tablet with DriveWizard Mobile
or DriveWizard installed is too far from the keypad.
Use the smartphone or tablet 10 m (32.8 ft) or nearer to the
keypad.
Note:
bCE
can occur when the smartphone or tablet is 10 m (32.8 ft)
or nearer to the keypad depending on the specifications of the
smartphone or tablet.
Radio waves from a different device are causing
interference with communications between the
smartphone or tablet and keypad.
Make sure that no device around the keypad uses the same radio
bandwidth (2400 MHz to 2480 MHz), and prevent radio
interference.
Note:
•
The drive detects this error when you use the Bluetooth LCD keypad to operate the drive from a smartphone or tablet.
•
Do a Fault Reset to clear the fault.
•
Set the stopping method for this fault in
o2-27 [bCE Detection Selection]
.
Code
Name
Causes
Possible Solutions
boL
BrakingTransistor Overload Fault
The duty cycle of the braking transistor is high (the
regeneration power or repetition frequency is high).
•
Install a regenerative converter.
•
Increase the deceleration time.
You enabled the protective function for the braking
transistor when you have a regenerative converter.
Set
L8-55 = 0 [Internal DB TransistorProtection Selection =
Disable]
.
The braking transistor in the drive is broken.
Replace the drive.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
bUS
Option Communication Error
The drive did not receive a signal from the
controller.
The communications cable wiring is incorrect.
Correct wiring errors.
There is a short-circuit in the communications cable
or the communications cable is not connected.
•
Repair short circuits and connect cables.
•
Replace the defective communications cable.
Electrical interference caused a communication data
error.
•
Examine the control circuit lines, main circuit lines, and
ground wiring, and decrease the effects of electrical
interference.
•
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
•
Use only the recommended cables or other shielded line.
Ground the shield on the controller side or the drive input
power side.
•
Separate the communication wiring from drive power lines,
and install a noise filter to the input side of the power supply
for communication.
•
Decrease the effects of electrical interference from the
controller.
The option is incorrectly installed to the drive.
Correctly install the option to the drive.
The option is damaged.
If the fault continues and the wiring is correct, replace the option.
Note:
•
The drive detects this error if the Run command or frequency reference is assigned to the option card.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, the drive will operate the motor as specified by the stopping method set in
F6-01 [Communication Error Selection]
.
Code
Name
Causes
Possible Solutions
CE
Modbus Communication Error
The communications cable wiring is incorrect.
Correct wiring errors.
There is a short circuit in the communications cable
or the communications cable is not connected.
•
Repair short circuits and connect cables.
•
Replace the defective communications cable.
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...