4 Installation
4.2.1 SERVOPACK Installation Environment
4-6
4.2
SERVOPACK Installation
4.2.1
SERVOPACK Installation Environment
Surrounding air
temperature: 0 to 55
°
C
Surrounding air
humidity: 90% RH or less (with no condensation)
Altitude: 1,000 m or less
Vibration resistance: 49 m/s
2
Note: The vibration resistance of a type A01 SERVOPACK with the mounting option is 4.9 m/s
2
.
Shock resistance: 147 m/s
2
Note: The shock resistance of a type A01 SERVOPACK with the mounting option is 19.6 m/s
2
.
Mounting in a Control Panel
• Installation in a System
To prevent the temperature around the SERVOPACK from exceeding 55
°
C, take into account the size of the
control panel, the layout of the SERVOPACK, and the cooling method.
• Mounting Near a Heating Unit
To prevent the temperature around the SERVOPACK from exceeding 55
°
C, suppress radiant heat from the
heating unit and temperature rise due to convection.
• Mounting to a Location Exposed to Corrosive Gas
Take measures to prevent exposure to corrosive gas. Corrosive gases will not immediately affect the SERVO-
PACK, but will eventually cause electronic components and contactor-related devices to malfunction.
• Other Locations
Do not mount the SERVOPACK in locations subject to high temperatures, high humidity, dripping water, cut-
ting oil, dust, iron filings, or radiation.
<Note>
When storing the SERVOPACK with the power OFF, store it in an environment with the following tempera-
ture and humidity:
• -20 to +85
°
C, 90% RH or less (with no condensation)