Getting Started
29
8
Turn the supply power back on.
9
Switch on power at the PSU switch.
2.4.3.4
Wiring Instructions for -48V DC PSU
Warning
The +48V and-48V terminals are not connected to chassis earth.
1
For installations with -48V earthed a shorting link must be added (see
Figure 2–10
).
2
For installations with a separate earth, connect the earth cable to the earth terminal (see
Figure 2–11
)
2.5 SBD Module Installation
2.5.1 Parts Check List
• 2 SBD Modules
2.5.2 Procedure
Important
Fibre Channel Host and Expansion Connectors:
If fitted with Optical modules, the modules must be a UL (or other North American NRTL)
RECOGNISED COMPONENT and the laser in the module must comply with Laser Class 1, US 21
CFR (J) and EN 60825-1.
If passive copper cables are connected, the cable must not have a connection to a common
ground/earth point.
1
Check for damage especially to the interface connector, do not install if any pins are bent
2
The modules should be installed in rear bays 3 and 4 of the Enclosure (
Figure 2–1
).
3
With the latch in the open position (see
Figure 2–12
), slide the SBD module into the enclosure until the
latch engages automatically.
Figure 2–10
Shorting Link
Figure 2–11
Separate Earth
Shorting Link
Earth Terminal