Troubleshooting
57
4.8.1.3
Removing a -48V DC Power Supply/Cooling Module
Warning
Do not remove the faulty Power Supply/Cooling (PSU) module unless you have a replacement unit
of the correct type ready for insertion.
Safety Requirements
Warning
Please refer to
2.4.3.1, ”-48V DC PSU Safety Requirements”, on page 25
before proceeding with
the following Removal procedures.
1
Switch off power at the PSU switch.
2
Remove all supply power by turning off the supply at the disconnect device located near to the equipment.
3
Remove the terminal block cover.
4
Disconnect the wires.
5
Replace the terminal block cover.
6
Squeeze the two latches on the PSU handle together and open the handle (see
Figure 4–6
) to cam the
Power Supply/Cooling module out of the enclosure.
7
Grip the handle and withdraw the module.(see
Figure 4–8
).
Figure 4–5
Removing/Inserting an AC Power Supply/Cooling Module (3)
Summary of Contents for RS-1600-FC-SBD
Page 6: ...vi RS 1600 1602 FC SBD User Guide...
Page 14: ...RS 1600 1602 FC SBD User Guide xiv...
Page 32: ...RS 1600 1602 FC SBD User Guide 18...
Page 47: ...Getting Started 33 Figure 2 15 Connecting Multiple Enclosures...
Page 58: ...RS 1600 1602 FC SBD User Guide 44...