Troubleshooting
59
4.8.1.4
Installing a -48V DC Power Supply/Cooling Module
Warning
Installation of this PSU module should only be performed by qualified personnel.
Safety Requirements
Warning
Please refer to
2.4.3.1, ”-48V DC PSU Safety Requirements”, on page 25
before proceeding with
the following Installation procedures.
1
Check for damage, especially to the rear connector on the Power Supply/Cooling module.
Caution
Handle the module carefully and avoid damaging the connector pins. Do not install the module if any pins
appear to be bent.
2
With the PSU handle (
Figure 4–7
) in the open position, slide the module into the enclosure.
Important
install the Power Supply/Cooling module in the right hand bay (Rear Bay 1) of the enclosure in an
“upside down” orientation.
3
Cam the module home by manually closing the PSU handle (see
Figure 4–8
). A click should be heard as
the handle latches engage (see
Figure 4–6
0.
4
Remove all supply power by turning off the supply at the disconnect device located near to the
equipment.
5
Remove the terminal block cover.
Figure 4–8
Removing/Inserting a -48V DC Power Supply/Cooling Module (3)