Features and Specifications
Specifications
24
Operating Manual for XKW 3kW Series Power Supply
Remote
Programming
and
Monitoring
Environmental
Specification
Remote Start/Stop and Interlock
TTL compatible input. Contact Closure,
12-250 Vac or 12-130 Vdc
Remote Analog Programming
Voltage and current programming:
0-5k resistances; 0-5V, 0-10V sources; 0-1mA
sources
OVP programming:
0-5V, 0-10V sources
Maximum Remote Sense Line Drop
Compensation
1 V max.
Operating Temperature Range
0-50 °C. From 50-70 °C, derate output 2% per °C
Storage Temperature Range
-55 °C to +85 °C
Humidity Range
Up to 80% non-condensing
Operating Altitude
Derate maximum operating temperature by 1°C
per 1,000 feet (30 m) for operation between
5,000 feet and (1,500 m) and 15,000 feet
(4,500 m)
Storage Altitude
Up to 50,000 feet (15,000 m)
Installation Category
II
Pollution Degree
2
TM-25OP-01XN.book Page 24 Monday, April 5, 2004 8:58 AM