ProAct P-Series FL Position Controller
Manual 26659
86
Woodward
Alarm or Shutdown Conditions
If the ProAct P-Series FL actuator has any alarm or shutdown conditions, refer to
Chapter 2 for details on the exact cause of the condition. The Service Tool must
be used to determine the cause of any shutdown or alarm condition. Refer also
to the ‘Troubleshooting Diagnostics Flags’ section above.
Discrete Output
If the discrete output is not functioning properly, verify the following:
Measure the output voltage on the terminal block. It should be in the range
of (10 to 28) V (dc) when the output is off/false. The status can be verified
through the Service Tool.
Check the wiring, looking for loose connections or disconnected /
misconnected cables.
Verify the configuration of the output.
Service Tool
If the Service Tool is not functioning properly, review the installation information
in Chapter 4. Verify the following:
Check the wiring, looking for loose connections or disconnected /
misconnected cables.
Check that Service Tool is running. Verify the Port setting is correct.
Follow on-screen error messages. Re-install software as needed. The latest
version of software is available for download from the Woodward web site
(
www.woodward.com/software.aspx
).