Manual 26659
ProAct P-Series FL Position Controller
Woodward
95
Serial Communication Service Port
Parameter
Value
Isolation None
Baud Rate Fixed 38.4 K baud
Maximum Cable Length 10 m (33 ft)—for service only (not intended for permanent
connection)
Cable Type Straight-through (no crossover)
CAN Communication Port
Parameter
Value
Wiring Specification
Isolation
ISO-11898, SAE J1939-11
None
Baud Rate Software configurable from 125 kbps to 1 Mbps
Electrical Interface CAN Hi and CAN Lo differential transmit/receive
Type Supports CAN2.0B and SAE J1939-11
Maximum Cable Length 30 m
Cable Type
Fault Detection
Two-conductor shielded cable according to SAE J1939-11
Software selectable. CAN Fault (Bus Off, Address Claim) and
Loss of CAN Demand provided.
Electronics Temperature (internal sensor)
Parameter
Value
Accuracy ±1 °C at 25 °C ambient
±2 °C over temperature range (–40 °C to +125 °C)
I/O Execution Rate 10 ms
Out of Range < –45 °C, >140 °C. Action is configurable in software