ProAct P-Series FL Position Controller
Manual 26659
74
Woodward
Data:
Byte 1
: Actual Valve Position
Data length:
1 byte
Resolution:
0.3922 %/bit, 0 offset
Range:
(0 to 100) % (0x00 to 0xFF)
Error Indicator not used.
Byte 2
: Desired Valve Position
Data length:
1 byte
Resolution:
0.39221/2.55 %/bit, 0 offset
Range:
(0 to 100) % (0x00 to 0xFF)
Error Indicator not used.
Byte
3-8
: Not Used (sent as 0xFF in each byte)
Diagnostics Message (Tx)—Legacy Mode
Transmission repetition rate: 100 ms
Data length:
8 bytes
Data Page:
0
PDU format:
FF
PDU specific:
10
Default priority:
6
PGN: 65296
(FF10)
Bit code legend
The following diagnostics and events status will be sent by the ProAct P-Series FL
actuator in a sequence.
Bit code
Description
00 Inactive
01 Active
10 Reserved
11 Not
Available
Bit position in a byte is “8 7 6 5 4 3 2 1”
Bit position 1 is the least significant bit.
Example: Bit position 2 is “1” and all others bits are “0”, byte value is 2.
Data:
Byte 1
: Diagnostic Indications 1
Bits 1-2: Stop commanded (Run/Stop)
Bits 3-4: CAN Position Demand Failed
Bits 5-6: Internal Fault
Bits 7-8: Analog Position Demand Failed
2
Byte 2
: Diagnostic Indications 2
Bits 1-2: PWM Position Demand Failed
2
Bits 3-4: not used (sent as 11)
Bits 5-6: General Alarm indication
Bits 7-8: General Shutdown indication
Byte 3-4
: Not Used (sent as 0xFF in each byte)
Byte 5
: Event Indications 1
Bits 1-2: Position Error
Bits 3-4: Temp Sensor Failed (>140 °C or <-45 °C)
1
Bits 5-6: not used (sent as 1)
Bits 7-8: 24 V Supply Out of Range (High or Low)
1