Manual 26659
ProAct P-Series FL Position Controller
Woodward
57
High
If “High” input type is selected, the switch must provide a high voltage on the
input, typically a switch to battery plus.
Low
If “Low” input type is selected, the switch must provide a low voltage on the input,
typically a switch to battery minus.
Closed
If “Closed” active switch is selected, the function is active when the contact is
closed.
Open
If “Open” active switch is selected, the function is active when the contact is
open.
Defaults: Active High, Active Closed
Outputs Section
Relay Output Configuration
The relay output can be configured to one of the following:
None
—The relay output is turned off.
On when selected faults become true—
Sets the relay driver to turn on
when the selected fault becomes true and turns off when no fault conditions
exist.
Off when selected faults become true—
Sets the relay driver to turn off
when the selected fault becomes true and turns on when no fault conditions
exist. This is the preferred, failsafe output configuration.
Default: None
It is recommended that the Relay Output be configured for the
failsafe ‘Off when selected faults become true’ mode, to ensure
maximum fault protection and annunciation. Failure to follow these
guidelines could, under exceptional circumstances, lead to personal
injury and/or property damage.
Relay Output Fault Selections
The list of faults displayed can be individually selected to activate the relay
output. A common selection is also provided to activate the relay output with any
configured Alarm or Shutdown fault.
Any of the selected faults will either turn the output off if configured for 'Off when
selected faults become true' or turn the output on if configured for 'On when
selected faults become true'.
Default: not selected