ProAct P-Series FL Position Controller
Manual 26659
38
Woodward
Position Setpoint
Displayed value of the position demand - in percent.
Actual Position
Displayed value of the actual position - in percent.
Setpoint Status
(conditionally displayed)
Indication of the position command redundancy status. Displayed only if the unit
is configured for redundant commands.
The following operating status indication is provided on the Service Tool and
over CAN.
Primary Demand Used
—indicates the primary demand is selected and the
backup demand is either not used or not failed.
Primary Demand Used, Backup Failed
—indicates the primary demand is
selected and the backup demand is failed, indicating the backup signal is
out of range or exceeds the demand difference from the primary.
Backup Demand Used, Primary Failed
—indicates the backup demand is
selected and the primary demand is failed. The failed may indicate the
signal is out of range or exceeds demand difference from the backup. Note
that the chosen input when the difference is exceeded is configurable.
Primary Enabled but not active
—indicates the backup demand is selected
but the primary demand will become active after a 10 second signal healthy
delay.
All Demands Failed
—indicates both the primary and backup (if used)
demands are failed (out of range).
Status Bar Indications
At the bottom of the Service Tool window is a status bar. The status bar has two
sections. The bottom left section displays communication status and bottom right
section displays alarm & shutdown status.
Communication Status
This section of the status bar shows the status of communication between the
Service Tool and the ProAct P-Series FL actuator.
Connected
—The Service Tool is connected to and communicating with the
actuator.
Not Connected
—The Service Tool is not connected to the actuator.
Connecting
—The Service Tool is attempting to connect to the actuator. This
message is displayed when Connect is selected from the Communications
menu or when attempting to re-establish communication to the actuator. If
the connection is lost, it will continuously attempt to re-connect.
Alarms and Shutdowns
Alarm
Status
One or more alarms on the Alarms screen are active.
Shutdown
Status
One or more shutdowns on the Shutdowns or Internal Shutdowns screen
are active.