ProAct P-Series FL Position Controller
Manual 26659
64
Woodward
Manual Calibration Summary
1. Safety warnings are read, followed, and acknowledged.
2. The direction is set to CW or CCW rotation.
3. The actuator shaft is positioned to the desired 0 % position point.
4. The actuator shaft is positioned to the desired 100 % position point.
5. The inertia and friction values are set. See the instructions below on
“Adjusting the Inertia Settings” and “Adjusting the Friction Settings”.
6. To check the position calibration, change the position setpoint and verify that
the actual position is correct. The endpoints of travel can be adjusted if
needed.
Automatic Calibration
1. Safety warnings are read, followed, and acknowledged.
2. The direction is set to CW or CCW rotation.
3. The actuator strokes itself in the minimum direction, then in the maximum
direction.
4. The inertia and friction values are set. See the instructions below on
“Adjusting the Inertia Settings” and “Adjusting the Friction Settings”.
5. To check the position calibration, change the position setpoint and verify that
the actual position is correct. The endpoints of travel can be adjusted if
needed.
Figure 6-2. Auto Cal Direction Screen
Click Next or Cancel.