Mechanical:
Travel
73 to 77 degrees
Weight
Model II
11 kg (25 lb)
Model III
15 kg (32 lb)
Model IV
24 kg (52 lb)
Mass Moment of Inertia
Model II MMOI
5.5E-4 kg-m² (4.9E-3 lb-in-s²)
Model III MMOI
6.4E-4 kg-m² (5.6E-3 lb-in-s² )
Model IV MMOI
8.2E-4 kg-m² (7.2E-3 lb-in-s² )
Power Supply Input
Parameter
Value
Normal
Operation
Transient/Starting
Max
Extended
Voltage
Min
Extended
Voltage
Max
Current
Transient
Max Current Continuous
Max Power Steady Continuous
Max Power Transient
(18 to 32) V (dc)
(8 to 40) V (dc) for 1 minute
40 V (dc) (1 minute)
8 V (dc) (limited performance)
Model II < 13 A @ 18 V
Model III < 15 A @ 18 V
Model IV < 20 A @ 18 V
Model II < 3.5 A @ 18 V
Models III & IV < 6.5 A @ 18 V
Model II - 65 W
Model III - 73 W
Model IV - 101 W
Model II - 251 W
Model III - 282 W
Model IV - 371 W
Hold Up Time
NOTE
: Depends on operating conditions.
1.1 ms at 24 V (dc) with max load
Out of Range Detection <9 V (dc) for 500 ms, <17 V (dc) for 70 s, >33 V (dc) for 500 ms.
Action is configurable in software.
Position Feedback Sensing (internal sensor)
Parameter
Value
Input
Circuit Output
Software Output
Accuracy @ 25 °C
Repeatability @ 25 °C
Temperature drift
Sample Rate
Out of Range Detection
~(1 to 4) V (dc) from Hall-Effect Sensor
~(0.5 to 4.5) V (dc) to analog-to-digital converter
0 to 75 degrees (1.31 radians) rotation, calibrated to actual
measured value
< 1.0 % of full travel
< 1.0 % of full travel
350 ppm/°C of full travel, maximum
1 ms
<0.012 V (dc) or >4.987 V (dc) for 5 ms