Manual 26659
ProAct P-Series FL Position Controller
Woodward
77
The ProAct P-Series FL only monitors the ‘Current Data Link’ bits of DM13 (bits
8-7 in byte 1) for Start/Stop commands and support for the DM13 ‘Suspend’
feature is not provided. A 'Start' command is a value of 01 on bits 6-7 of byte 1, a
'Stop' command is a value of 00 on bits 6-7 of byte 1, and a 'Hold' command is a
value of 00 or 01 on bits 4-7 of byte 4.
While a DM13 commanded 'stop' is active, the CAN demand is internally set to
zero and any CAN demand timeout will not be recorded. The commands shall be
processed as follows in the event multiple commands are determined in the
same message. When in QUIET/Stop mode, a Start shall have priority over a
Hold and additional Stop commands are ignored. When not in QUIET/Stop
mode, Start and Hold commands are ignored.
DM13 Message
Data length:
8 bytes
Data page:
0
PDU format:
223 (DF)
PDU specific:
DA (responds to specific SA or global)
Default priority:
6
Parameter Group Number:
57088 (DF00)
Data:
Byte 1:
Bits 1-2: (ignored)
Bits 3-4: (ignored)
Bits 5-6: (ignored)
Bits 7-8:
Current Data Link
(see bit code legend 1 below)
Byte 2:
(ignored)
Byte 3:
(ignored)
Byte 4:
Bits 1-2: Suspend Signal (not supported)
Bits 3-8:
Hold Signal
(see bit code legend 2 below)
Byte 5-6:
Suspend Duration (not supported)
Byte 7-8:
SAE Reserved (not used)
Bit code legend 1
Bit code Description
00 Stop
Broadcast
01 Start
Broadcast
10 Reserved
11
Don't care/take no action
Bit code legend 2
Bit code
Description
0000 All
Devices
0001 Stopped
Devices
0010-1110 Reserved
1111 Not
available