Message Settings Section
ECU Instance
Displays the value of the ECU Instance in the J1939 Name. This is displayed for
informational purposes only.
Enable Legacy Message Mode
Selects either Legacy messages (checked) or configurable PGN messages
(unchecked), for each harness code address (Unit 1-4).
Default: checked
Function Field
Sets the J1939 Name function field for each harness code address (Unit 1-4).
Allowed values: 0 to 255. Defaults: 146, 144, 142, 144
Source Address
(only displayed if Legacy Mode is not selected)
Sets the J1939 source address for each harness code address (Unit 1-4). In
legacy mode this setting is fixed based on the harness ID with values 19, 20, 21,
22 (see Chapter 7).
Allowed values: 0-253. Defaults: 34, 128, 129, 130
Data Message PGN
(only displayed if Legacy Mode is not selected)
PGN for the data message transmission for each harness code address (Unit
1-4). Only used when configurable PGN messaging is used.
Allowed values: 0-65535. Defaults: 65516, 65517, 65518, 65519
CAN Position Command Settings Section
(only displayed if CAN demand
is configured)
This section provides settings related to a J1939 CAN commanded position
setpoint.
Command Message PGN
(only displayed if Legacy Mode is not selected)
PGN for the expected incoming command message for each harness code
address (Unit 1-4). Only used when configurable PGN message is used and
CAN position demand is configured.
Allowed values: 0-65535. Defaults: 65306, 65307, 65308, 65309
CAN Fail Timeout
Sets the maximum allowed delay, ins seconds, between CAN received position
command messages before a CAN Demand Failed diagnostic is annunciated.
Allowed values: 0.010-10 seconds. Default: 0.035 seconds