EGCP-2 Engine Generator Control Package
Manual 26174
86
Woodward
Engine Control
Preglow Time
Time of preglow allowed prior to engine crank cycle.
Maintained through engine cranking.
Resets after every crank attempt.
Crank Time
Maximum Allowable Time for Engine Cranking.
Crank Cutout
Engine rpm level where crank command is canceled.
Crank Delay
Time between Engine Crank Attempts.
This Delay is started when in the Spindown mode and the speed of the
generator set has dropped below 50 rpm. Cannot restart engine until this
time has expired.
Crank Repeats
Number of times EGCP-2 will repeat its attempt to start the engine.
Cranking attempts will equal the value of Crank R1.
Crank Fail
Alarm Set Point.
Activates when the Number of Crank Repeats is depleted.
Idle Speed
If the Relay #12 output is configured for Idle/Rated switch, this value will set
the speed at which the Idle/Rated Time begins.
Value should be approx. 10% less than the actual idle speed of the
generator set.
Idle Time
The delay in seconds the EGCP-2 waits once the Idle/Rated Speed set
point is exceeded. Once the Idle/Rated Time is passed, the EGCP-2 will
energize the #12 Discrete Output (if the Relay #12 output is configured for
the idle/rated function).
Cooldown Time
Time allowed for cooldown once engine achieves a stop cycle.
Must exceed Cooldown Limit (see next display) before activated.
Cooldown Limit
kVA set point at which, when exceeded, will cause the engine to go to a
cooldown during the next stop cycle.