EGCP-2 Engine Generator Control Package
Manual 26174
8
Woodward
There are a total of 19 keys on the keypad. Each key has the following
function(s):
ALARM/EVENT LOG KEYS:
ALARM / EVENT
The ALARM/EVENT key is used to access the Event
log. When pressed, the current alarm events will be displayed on the right hand
LCD screen. When multiple alarms are logged, the up and down scroll keys will
allow you to navigate within the Event log. The Event log will store up to 16
events, as more events happen the oldest alarms will be dropped off to make
room for the newer events. If power is cycled to the control, the Event log will be
cleared.
ALARM CLEAR
The ALARM CLEAR key is used to acknowledge and
clear alarm events from the Event log. To acknowledge and clear alarm and
shutdown events a Security Code of Operator Level or higher is needed. After
selecting the ALARM/EVENT key:
If the Alarm mode is Visual or Warning—
1. Pressing the ALARM CLEAR key will acknowledge the selected alarm, this
means the cursor will move from the Alarm Name line down to the Time and
Date line.
2. Pressing the Alarm Clear key a second time will remove the event from the
log.
If the Alarm/Shutdown mode is Audible, Soft Shutdown, or Hard Shutdown—
1. Pressing the ALARM CLEAR key once will de-energize Discrete Output #11,
Audible Alarm. This will happen without selecting the ALARM/EVENT key
and without a Security Code entered.
2. With the ALARM/EVENT key pressed, so the Event log is being displayed:
Pressing the ALARM CLEAR key a second time will acknowledge the
selected alarm. This means the cursor will move from the Alarm Name line
down to the Time and Date line.
3. Pressing the Alarm Clear key a third time will remove the event from the log.