Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
99
Engineering
unit
selections
Displayed Units
o
Ma
o
V
o
kW
o
MW
o
kVA
o
MVA
o
kVAR
o
MVAR
o
PF
o
Deg
C
o
Deg
F
o
PSI
o
kPA
o
BAR
Process Low Value
The Process Input, when at 4 mA or 1.0 volt, will be displayed as.
o
Example:
Process Low Value = –1000 kW
Process Input is 4 Ma
KW LOAD status screen will display: –1000 kW
Process High Value
The Process Input, when at 20 mA or 5.0 volt, will be displayed as.
o
Example:
Process High Value = 750 kW
Process Input is 20 Ma
KW LOAD status screen will display: 750 kW
Sample Process Applications with Process Units as kW and mA:
kW Transducer Input = 4-12-20 mA
4 mA = –500 kW
12 mA = 0 kW
20 mA = 500 kW
Process Units
kW
Process Action
Indirect
Process Deadband
0.3 %
Process Ref
–50 kW (Import Power)
Process High Limit
100 kW
Process Low Limit
–250 kW
Process Low Value
–500
Process High Value
500
Process Units
mA
Process Action
Indirect
Process Deadband
0.3 %
Process Ref
11.5 mA (Import Power)
Process High Limit
14 mA
Process Low Limit
10 mA
Process Low Value
4
Process High Value
20