
Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
61
Figure 4-6. I/O Status
IN
: Discrete Inputs 1 through 16.
OUT
: Discrete Outputs 1 through 12.
Volt Bias
: % voltage bias output (±100% range).
Speed Bias
: % speed bias output (±100% range).
Process In
: Process Input will be displayed in Engineering Units configured in
the Process menu. Shown in Milliamps.
Discrete Inputs
1. Automatic Switch
2. Test Switch
3. Run with Load Switch
4. Volts Raise
5. Volts Lower
6. Speed Raise
7. Speed Lower
8. Gen Circuit Breaker Aux Contact
9. Mains Circuit Breaker Aux Contact
10. Process Switch
11–16. Remote Alarm/Shutdown
Inputs
Discrete Outputs
1. Mains Breaker Close/Contactor
Close
2. Gen Breaker/Contactor Close
3. Engine Preglow
4. Fuel Solenoid
5. Engine Crank
6. Visual Alarm Relay
7. Local Bus PT Connect
8. Mains PT Disconnect
9. Mains Breaker Trip
10. Gen Breaker Trip
11. Audible Alarm
12. kVA load switch, or Idle/Rated
Switch, depending on configuration